High-density data centers, driven by artificial intelligence, are changing the fire risk profile. Work on NFPA standards is underway: it is important to distinguish between what is already in effect and what is still a proposal.

Data centers are now an essential component of economic infrastructure. The cloud, financial services, telecommunications, healthcare, industry, public administration, and—increasingly—artificial intelligence applications all depend on facilities that must guarantee extremely high availability. This central role also changes the risk profile: electrical density—that is, the amount of energy concentrated within buildings—is increasing, as is the complexity of cooling systems and the economic value of the installed equipment. This issue has been incorporated into the revision of NFPA standards. Before delving into the details, here is a distinction that will be useful to readers.

  • Already in effect: NFPA 75 (2024 edition) and NFPA 855 (2026 edition), which has already introduced stricter fire testing requirements for energy storage systems.
  • Still under discussion: the public inputs submitted during the current revision cycle for NFPA 75 and NFPA 76. A public input is a proposal from an individual; it is neither a decision by the technical committee nor a requirement.

NFPA 75 and High Density

The most important standard is NFPA 75, Standard for the Fire Protection of Information Technology Equipment, which addresses fire protection for modern data centers. Among the public comments submitted to the technical committee, one of the most significant points concerns power density: data centers for high-performance computing and artificial intelligence applications can exceed 30 kW per rack, and liquid cooling solutions achieve even higher densities. The issue is not just about energy consumption. The increase in power density also changes the conditions under which fire protection systems must operate. The number and density of piping, electrical networks, and data connections are growing, which complicates the distribution of water from sprinklers and increases the value concentrated in each rack. According to one of the public comments, in high-density data centers, potential damage stems not only from fire but also from the difficulty of responding effectively without damaging extremely valuable equipment.

Artificial intelligence is also changing fire protection

The development of artificial intelligence has accelerated the process. GPU servers for AI and high-performance computing generate much higher thermal loads than traditional data centers and are driving the shift from air cooling to liquid cooling, particularly cold plates (also known as direct-to-chip) and immersion cooling. These systems can improve energy efficiency, but they introduce new considerations from a safety perspective: the presence of liquids in server rooms, the risk of leaks, interaction with uninterruptible power supplies (UPS) and lithium batteries, ventilation methods, and compatibility with fire suppression systems. This is an example of how a technology introduced to solve an operational problem can create new dependencies and new risk scenarios.

A dedicated working group: a proposal, for now

A public comment submitted during the 2026 cycle sums up the issue well: the data center sector is evolving faster than regulations and standards. It therefore proposes a working group dedicated to new configurations, including modular structures, immersion cooling, high-voltage power distribution, energy storage, and other emerging technologies. It’s not just about protecting the building. The proposal calls for fire suppression, alarms, energy storage, and cooling to be considered components of a single safety system. Whether and how the committee will adopt it will be seen in the draft standards: until it appears there, it remains a proposal. It is, however, an indication of the direction we’re heading. In modern data centers, fire protection can no longer be a standalone subsystem. It must be integrated into the electrical architecture, cooling systems, battery management, equipment layout, and business continuity strategies.

Emergency Power Supply and Business Continuity

The availability of electrical power remains one of the key elements of data center resilience. NFPA 110, Standard for Emergency and Standby Power Systems, governs systems designed to provide emergency and standby power when the normal grid is unavailable. For a data center, however, the availability of a generator alone is not sufficient to ensure operational continuity. One must consider load transfer capacity, runtime, maintenance, fuel availability, cooling capacity during emergency operation, and the possibility that a physical event could compromise multiple components in the chain simultaneously. Reliability depends on the entire system, not on a single redundant component.

Energy Storage: New Resilience, New Risks

Energy storage systems are becoming increasingly important in digital infrastructure. NFPA 855, the Standard for the Installation of Stationary Energy Storage Systems, specifically addresses the risks of fire, uncontrolled overheating, the formation of flammable gases, and explosion associated with these systems. The 2026 edition, which has already been published, has tightened the testing requirements. It requires that a representative system undergo both UL 9540A testing and large-scale fire tests to demonstrate that a fire in one unit will not spread to an adjacent unit. It also makes Hazard Mitigation Analysis a basic requirement. It is still the ambivalent relationship between reliability and risk. Batteries increase the infrastructure’s ability to withstand a power outage, but they introduce a new hazard that must be considered during the design phase, compartmentalized, identified, and managed.

Cybersecurity is also part of fire protection

Another indication comes from NFPA 76, Standard for the Fire Protection of Telecommunications Facilities. In the 2026 revision cycle, it was proposed to include cybersecurity among the factors to be considered in the fire protection program. The rationale is clear: software and digital systems are increasingly performing functions related to power supply, load management, and temperature control. A cyberattack could therefore compromise systems that affect fire risk, and a fire could in turn jeopardize cybersecurity and data protection measures. This is a concrete example of the convergence of physical and digital risks.

For those working in Italy

The NFPA is a U.S. organization, and its standards are voluntary in Italy: they are not legally binding for an Italian data center. They remain a widely used technical reference, especially among international operators and insurers. The binding regulatory framework for an Italian operator is the Fire Prevention Code (Ministerial Decree of August 3, 2015) along with the requirements set by the competent authority; from a technical and infrastructure standpoint, the EN 50600 series on data center facilities is widely adopted. From a regulatory standpoint, data center service providers are classified as digital infrastructure under NIS2. The NFPA is also planning a webinar on data center safety for October 8, 2026, dedicated to current codes and standards regarding design, inspection, implementation, and emergency measures, along with a summary of the results of current research.

From Fire Safety to Digital Resilience

For those working in the field of resilience, this is the most interesting aspect. A data center can have sophisticated IT redundancies and still be vulnerable to a fire, a power outage, a cooling failure, or a problem with energy storage. The availability of digital services depends on a very tangible physical chain: power supply, cooling, fire protection, telecommunications, batteries, maintenance, and emergency response capabilities. The transformation of data centers, driven by AI and high-performance computing, makes this correlation even more evident. Power output increases, but so do energy density, system complexity, and the value concentrated within them. Ongoing work on NFPA standards—some of which are still in the proposal stage—points to a principle that goes beyond fire safety: digital resilience cannot be separated from the physical resilience of the infrastructure that makes it possible.

Questions for Resilience Managers

  • Is our data center—or our provider’s data center—designed with an integrated approach to fire protection, power, cooling, and energy storage, or as separate subsystems?
  • Have we assessed the impact of liquid cooling and lithium-ion batteries on the level of continuity we promise?
  • What does the contract with our supplier stipulate regarding fire risk and the tests performed?
  • If a fire were to simultaneously take out a site’s server room, UPS, and cooling system, how long would our backup power last?

Sources